HOTUpgrade dual meter service panel
Permit #TC-RES-0826-04854 · tucson · issued Sep 5, 2026
~$5,766est
Issued
0Done Rite Services LLC (Likely)
Maricopa County · APN 113021600
Tucson, AZ, 85719
vf-This permit application will be voided. It appears there is a duplicate permit application (TC-RES-0826-04854). Please see review comment and resubmit under the existing permit TC-RES-0826-04854. Provide the model number of the SPD to be installed. The SPD must have a nominal discharge current rating of not less than 10 kA, be UL 1449 listed, and be Type 1 or Type 2, per 230.67. Resubmittal Instructions: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf Upgrade 200AMPG service to 100 AMP service meter.